Wiring: JP Series with the RY-3DL

You are here:
Estimated reading time: 1 min

Summary

The JP-4MED can release up to 4 doors when using one RY-3DL and one RY-24L. The first 3 doors will be triggered by the RY-3DL using door release output 1. The 4th door will be triggered by the RY-24L using door release output 2.

 

Wiring Diagram

Settings on Master

The door release buttons on the JP-4MED master will need to be programmed so that release button 1 will be selectable while doors 1, 2, and 3 are active and release button 2 will be selectable while door 4 is active. Enter the Install Menu. Press and hold the Home button and then tap SETTINGS, then INSTALL. A warning message will show on the screen. Tap ENTER to enter the install menu.

Make sure you continue to hold the Home button during this process or you will be returned to the starting screen.

 

From the Install Menu, tap SET DOOR RELEASE. Tap LOCK1 to change the settings for relay 1.

 

  1. Tap OUTPUT METHOD and select if relay 1 will be a N/O or N/C contact.
    Set to N/O when using the RY-3DL.T
  2. Tap REFERENCE DOOR and choose to “Show” or “Hide” the door release 1 icon for each door station.
    For the drawing on page 1, the door release 1 icon should be shown for doors 1, 2, and 3 and hidden for door 4.
  3. Tap DOOR RELEASE DURATION to set the door release time for contact L1. The default “momentary” setting will be used when connecting to the RY-3DL.

When done, tap the BACK button to return to the SET DOOR RELEASE page. Repeat the process for LOCK2. When referencing doors, hide doors 1, 2, and 3 and show door 4 for door release icon 2.

 