LEF
System Trouble Shooting
Trouble Shooting
Flowchart:
Master to Audio Only Sub
1. New LEF with All Call adapter has more than one
light coming on when subs call in.
1. Check to see if "E" & "-"
wires are shorted together anywhere in the system.
2. Capacitors (NP-25V) are required between master and All
Call adapter, in series with each station number terminal assigned to an indoor sub
station.
Refer to BGR-10A
Instructions. Refer to BG-10C Instructions. Refer
to LEF-C Instructions. Refer to LEF Instructions.
2. New LEF system has buzz or hum.
Master(s) is too close to AC voltage or dimmer switches.
Shielded wire is recommended. If shielded wire was run, tie all of the shields together
and ground one end to an earth ground.
Wire between master stations must be in one
jacketed cable. If multiple cables were used, make sure all station number wires and the E wire are
in the same jacketed cable.
Refer to LEF-C
Instructions. Refer to LEF Instructions
3. New LEF system has more than one light coming on
when subs call in.
1. In a multiple master system, make sure that the "E" & "-" are not shorted together.
Refer to LEF-C
Instructions. Refer to LEF Instructions
2. Possible power surged units, send in for repair.
4. Existing LEF system has more than one light
coming on when subs call in.
Possible power surged units, send in for repair.
5. LEF one master system, communication with the
sub is fine, but no call tone (or call tone but no communication or a combination of both
at different subs).
If running 2 conductors to sub stations: Jumper between
"E" & "-" has been removed and must be reinstalled on all units,
including master station.
Refer to LEF-C
Instructions. Refer to LEF Instructions
6. LEF system, "Occupied" light always
on.
A station in the system is in the "ON" position,
the "R" wire is shorted, or a unit in the system is damaged.
Refer to LEF-C
Instructions. Refer to LEF Instructions
7. LEF system, no communication between masters.
Improper connection of the "C" terminal.
("C" Stands for "call", not "common"). Check wiring
connections between master stations to make sure the wire on the "C" terminal is
wired properly. "C" of master 1 connects to 1 of all other masters.
"C" of master 2 connects to 2 of all other masters, etc.
Refer to LEF-C
Instructions. Refer to LEF Instructions.
8. LEF/BGR, no audio or music but has lights &
shows display.
PS-1225UL (or PS-12C) and PS-2410A
(or PS-24C) power supplies might be swapped. 12V DC
power goes to LEF, 24V DC goes to BGR-10A.
Refer to BGR-10A
Instructions, BG-10C Instructions, LEF-C Instructions or LEF
Instructions.
9. LEF/BGR, music gets louder when selecting a
station from a master.
"R" or the "12V -" are not connected
from the LEF to the BGR-10A.
Refer to BGR-10A
Instructions, BG-10C Instructions, LEF-C Instructions or LEF
Instructions.
10. LEF System, "All Call" isnt
working.
1. All call requires additional equipment (BGR-10A with
PS-2410A, or BG-10C with PS-1225UL).
Refer to BGR-10A
Instructions, BG-10C Instructions, LEF-C Instructions or LEF
Instructions.
2. If additional equipment is present, check for proper
connection of P1, P2, and P3 terminals from the master stations to the BG-10C or BGR-10A.
Refer to BGR-10A
Instructions or BG-10C Instructions.
11. LEF system with All Call/music, subs
continuously call in if music is on or all call is attempted (LE-A/AN, LE-B/BN, LE-D/DA
sub stations only).
The system requires one NP-25V capacitor for each sub
station. Install capacitor in series on all sub station number terminals between the LEF
master and All Call/Music adapter.
Refer to BGR-10A
Instructions, BG-10C Instructions, LEF-C Instructions or LEF
Instructions.
12. LEF System with BGR-10A/BG-10C door station
does not chime when call button is pressed.
Check for proper connection of the DA/DB/DC terminals and
the 12V DC "-" between BGR-10A/BG-10C and LEF master. Number wire (1) from door
station must be connected to DA, DB, or DC terminal. Negative of LEF must be connected to
- of BGR-10A. "E" is common communication. Chime tone is generated by a
momentary closure between 1 & - of door station, activating chime by shorting DA to -
in BGR-10A (BG-10C).
Refer to BGR-10A
Instructions, BG-10C Instructions, LEF-C Instructions or LEF
Instructions.
13. LEF System with BGR-10A/BG-10C door chimes when
call button is pressed, however the electronic call tone is heard as well.
Door station must tie to the BGR-10A/BG-10C first. Also,
SW-5 on the back of the main PC board needs to be in the "A" position (on all
LEF series masters). LEF-C masters come in the "A" position from the factory.
LEF surface mount units come in "B" position, and must be changed to
"A" when used with BG-10C.
Refer to BGR-10A
Instructions, BG-10C Instructions, LEF-C Instructions or LEF
Instructions.
14. LEF System, the door release doesnt
function.
The LEF requires an RY-PA relay for each door being
released. Two black wires are input side, requiring 12V DC to activate relay. Two yellow
wires provide a normally open dry closure when the relay is activated.
Refer to LEF Instructions.
15. LEF/MY system has a
buzz or hum.
1. Connect "G" terminal on the PS-1820UL
power
supply to an earth ground.
2. Make sure that the MONITOR is on the left-hand side of the LEF intercom when facing the
units.
3. Make sure the video wiring (18AWG, 6 conductor) is run in a separate jacketed cable
from the intercom wires, and that the intercom wiring is not run directly behind or near
the video monitor.
Refer to MYW-P3L
Instructions, MYW-P1L Instructions, LEF-C Instructions or LEF
Instructions.
16. LEF/MY system has a buzz or hum when the
monitor is on.
Monitor has to be on the left side of the LEF master.
(it
cannot be on the right.) Also, ground the PS-1820UL terminal to the
PS-1225UL. Refer to
#15.
17. LEF/ MY system, proper door camera comes on
when the call button is pressed, however all video and communication is lost when the
station is selected.
1. "K" terminals are improperly connected or not
connected at all.
Video door stations 1, 2, and 3 correspond to DA/KA, DB/KB, and DC/KC terminals
accordingly. E.g. If door #1 is on channel 10, K10 of master station must be connected to
KA of MYW-P3L. Likewise for other stations.
Refer to MYW-P3L
Instructions, MYW-P1L Instructions, LEF-C Instructions or LEF
Instructions.
18. LEF/ MY system, proper door camera comes on
when the call button is pressed, however there is no control of the pan and tilt
functions.
1. Wire gauge is too thin or power supply is too far
away. Make sure power supply is within 16' of the adaptor or
monitor and is connected using 18 AWG wire.
2. Take affected unit to "working" location or to
the MYW Adapter and test.
Refer to MYW-P3L
Instructions, MYW-P1L Instructions, LEF-C Instructions or LEF
Instructions.
19. Monitor does not turn on when door station call
button is pressed.
1. Take a voltage reading between U1 and -. It should
be roughly 18V DC. Check connection between MYW adapter and MYH monitor to make sure +, -,
U1, and U2 terminals are connected properly.
2. Short U2 to - at monitor, and the monitor should turn
on.
3. Short U2 to - at the previous monitor or MYW adapter to
isolate the problem to wiring or equipment.
Refer to MYW-P3L
Instructions, MYW-P1L Instructions, LEF-C Instructions or LEF
Instructions.
20. LEF/ MY system, no call tone from camera.
Perform jumper test at LEF Master (short station number to
"-"). If call tone is heard, repeat jumper test on the appropriate D
terminal (DA, DB, DC) and "-" at the MYW Adapter. If call tone is heard,
perform jumper test at appropriate A1, A2 terminals. If call tone is heard, take
wires off of camera and short together. If that works, then the call button in the camera
is malfunctioning.
Use jumper tests as described to isolate problem to
specific equipment or wire.
Refer to MYW-P3L
Instructions, MYW-P1L Instructions, LEF-C Instructions or LEF
Instructions.